This is only a preview of the November 1987 issue of Silicon Chip. You can view 42 of the 96 pages in the full issue, including the advertisments. For full access, purchase the issue for $10.00 or subscribe for access to the latest issues. Articles in this series:
Articles in this series:
Items relevant to "1GHz Digital Frequency Meter":
Articles in this series:
Items relevant to "Your House Wiring Could Kill You":
Articles in this series:
Articles in this series:
|
Your house
Virtually every household in Australia
uses M.E.N. and it is assumed to be a
very safe system. But it is not foolproof.
Unless checked out from time to time,
it can develop a very dangerous fault.
By LEO SIMPSON
M.E.N. stands for "multiple earth
neutral" and is the system used for
wiring the majority of domestic
electrical installations in Australia.
As specified in the SAA Wiring
Rules (AS 3000-1986), the mains
neutral wire is connected to earth
at the user's switchboard. In most
houses this means that the 240V AC
mains supply is connected from the
power pole in the street via via two
cables, active and neutral, with the
neutral wire connected to earth via
the consumer's water pipe.
The earth connection point on the
water pipe is usually just at the
point where the pipe enters your
house. This is important because
you need to examine it occasionally
to make sure that the connection is
sound. As we will show, that connection is vital to the safety of
everyone in your household.
Typically, the active and neutral
25A SWITCH
WATT-HOUR
METER
oiriN~RE~r
FUSE
l--,U.-'0---TO OFF PEAK HOT
WATER SYSTEM
6OA SWITCH
NEUTRAL
LINK
SWITCH
BOARD
Fig. 1
76
SILICON CHIP
EARTH TO
CONSUMER 'S -:WATER PIPE
• • g
wires from the power pole to your
house have a capacity of 70 or 100
amps. This means that the maximum electricity consumption (volts
multiplied by amps) for the
household is nominally 18.9
kilowatts in the case of 70 amp
mains and 24 kilowatts in the case
of 100 amp mains.
Happily, most homes normally
use only a small fraction of their installed wiring capacity although
there would be times during winter
evenings when it could be easily approached in large households when
several radiators, a stove and
perhaps one or two other cooking
appliances are in use.
Why M.E.N?
"Multiple earth neutral" is a
system which offers improved safety and lower losses in energy
transmission. Let's see why.
In a normal single-phase 240V AC
wiring system (which is what most
households have), the nominal
voltage of the neutral wire coming
into your switchboard is the same
as earth, ie, zero volts. But in practice, the voltage is higher because
all the current from your house and
your neighbours' homes inevitably
causes a voltage drop in the neutral
ea ble between your power pole and
the nearest substation or pole
transformer.
This is because the resistance of
the neutral cable is not zero and so
the large currents inevitably mean
that there is some voltage present
on the neutral. This voltage is a loss
in the energy transmission system
and is part of the reason why, when
At left is a diagram depicting the
electrical switchboard of a typical
household using the "multiple earth
neutral" system.
could kill you!
The mass of connections to a typical power pole. The neutral return to the
substation is the cable to which all consumers are connected (ie, top of photo).
Other earthing systems
There are two other systems for
earthing of consumer electrical installations in Australia. One is known
as Direct Earthing while the other ·is
referred to as ELCB or Earth Leakage
Circuit Breaker. In the Direct Earthing
system, the earth wires of the installation are connected to earth via a water
pipe or electrode but do not connect
to the neutral conductor at the
switchboard.
In the ELCB system, there are two
connections to earth with a sensistive
relay coil connected between the two .
If a fault current flows to earth, the
energy demands are heavy, the
mains voltage available at your
switchboard is lower than it should
be, or would be if it were not for the
multiple earth neutral system.
Because the neutral wire is connected to earth (ie, the consumer's
water pipe), there are actually two
return paths for the current pass-
potential difference between the two
earths will trip the circuit breaker and
disconnect the mains supply. Again, in
the ELCB system there is no connection between the consumer's earth
and the neutral conductor at the
switchboard .
Throughout most of Australia the
ELCB system has been superseded
by the MEN system described in the
article. The ELCB system was prone
to false tripping and improved safety
can now be provided by using the
MEN system combined with core
balance relays.
ing through the appliances in your
home.
Some of the current passes back
along the neutral, back out to the
power pole and thence via the
power lines back to your local substation, pole transformer or
whatever. The rest of the current
passes back via the earth wire to
the water pipe and then via good
old Terra Firma itself to the
substation.
(Editor's note: we have simplified
matters here by ignoring the inherent current balance of threephase power energy distribution
systems. For a brief explanation,
see the panel headed, "Current
flow, three-phase and all that".)
If you are not familiar with the
mains distribution system this may
all sound like heresy but it is true.
Have a look at Fig.1 which depicts
the mains wiring of a typical
household installation.
This diagram shows the active
and neutral connections to the switchboard. The active wire is connected via two watt-hour meters
one feeding the off-peak hot water
service and the other feeding the
rest of the power circuits in the
household.
Following each watt-hour meter
is a large rotary or toggle switch
which is typically rated at around
60 amps and is connected via a
short length of cable to the Active
link. This is a heavy brass bar with
quite a few screw connections to
take the wires feeding the fuses or
individual circuit breakers. The
whole Active Link assembly is housed under a plastic cover to avoid
accidental contact by anyone who
has access to the switchboard.
A typical modern houshold may
have one 25-amp circuit to feed the
stove and oven, three 15-amp circuits to feed all the power points
and two or three 8-amp circuits for
all the lights. By the way, in the wiring standards, power points are
referred to as GPOs which stands
for General Purpose Outlet.
All the neutral return wires from
the household power and lighting
circuits are connected together at
the Neutral link which is a similar
assembly to the Active Link. The
difference is that the Neutral link
NOVEMBER 1987
77
What's available in
clamp-on current meters
The Escort ECT-620 has two DC
and two AC voltage ranges, two
resistance ranges and three
current ranges up to 1000 amps
AC. It is priced at $155 (tax incl)
from Emona Instruments. Phone
(02) 519 3933.
The Emtek DCT-300 has three DC
and two AC voltage ranges, four
resistance ranges and three
current ranges up to 400 amps
AC. It is priced at $141.92 (tax
incl) from Geoff Wood
Electronics. Phone (02) 427-1676.
What's in a
clamp-on meter
The typical clamp on current
meter is a current transformer
with a turns ratio of 1 : 1000
with the laminated steel clamp
providing the magnetic core of
the transformer.
With the clamp placed around
a cable carrying 1 0 amps AC,
the secondary will generate 1 0
milliamps. In analog clamp
meters the secondary current is
rectified and read on a moving
coil meter. In digital clamp
meters the secondary current is
applied to a shunt resistor and
the resulting voltage is read by
the digital metering circuitry.
Some clamp-on adaptors for
digital multimeters will measure
DC as well as AC by using Hall
effect sensors.
78
SILICON CHIP
The Escort ECT-620 has one AC
voltage range, one resistance
range and two current ranges to
300 amps AC. Priced at $118 (tax
incl) from Emona Instruments.
Phone (02) 519-3933.
also carries all the earth wires
from the power and lighting circuits
as well as the main earth wire
which connects to the water pipe. It
also connects to the neutral wire
which comes directly from the
power pole.
So there is a straightforward circuit and it would be natural to
assume that all the current which
comes in via the active feed wire
goes out via the neutral wire. In
other words, the current in the active wire is equal to the current in
neutral wire. Well, it ain't
necessarily so. It is possible that
half or more of the return current
goes via the Earth wire and the
remainder goes via the neutral
back to the power pole.
To take a particular example, if
you were using a 2400 watt
radiator which draws 10 amps
from the active line, 8 amps might
go via the earth wire to the water
pipe and the remainder, 2 amps,
would go via the neutral return.
The simple explanation for this is
that the resistance of the neutral
cable back to the substation or pole
transformer is slightly higher than
the very low resistance via the
earth path to the same point. Ergo,
some current goes via Earth and
some goes via neutral. It can't all go
via neutral.
Having come to terms with this
previously unconsidered fact, what
does it mean? It means that the supply authorities are able to obtain
lower supply losses in the return
path than they otherwise would if
the MEN system was not used. They
also experience less voltage
flashovers from neutral to Earth
during thunderstorms in appliances
which are permanently connected.
A common example of this used
to occur in stove heating elements.
Even though the stove or oven might
have been turned off, a lightning
strike on a power line would cause
many stove elements to break down
to chassis. With the MEN system
this is not a problem.
Where lie the problems?
Corrosion is the first problem.
Since many small appliances these
days use thyristor power controls
there is inevitably a DC current imposed on the mains supply. Some of
This shot shows Tandy's Micronta clamp-on meter measuring the current in an earth wire to a water pipe. The
present model has two AC voltage ranges from 6 to 300 amps AC, and is available from all Tandy stores for $64.95
(Left hand by courtesy of Greg Swain - the rest of him has been edited out.)
this direct current will flow via the
connection between the earth wire
and the water pipe. And the very
presence of DC will accelerate corrosion which naturally occurs when
dissimilar metals are used, as they
normally are.
Ultimately, corrosion of the connection between the Earth wire and
the water pipe will mean that the
connection will be broken. Or if it
does not physically break, its
resistance will be so high as to be
useless.
OK, so that means that if you
have lost the Earth connection and
an appliance such as your washing
machine breaks down from active
to chassis, the chassis could be
lethal. That is bad enough but consider another possibility which is
even more likely and which has occurred a number of times quite
recently in Sydney.
If corrosion has occurred in the
connection between your main
Earth wire and the water pipe, is it
not just as likely that corrosion has
progressed in the neutral connections between your house and the
power pole? Of course it has. What
that means is that the neutral
return could now have an appreciable resistance and could
easily be around 20 ohms or more.
If that is the case, all of the return
current will go via the Earth and
water pipe.
But what if the earth connection
has broken? What that means is
that if you now have an appliance
drawing 5 amps, the voltage impressed across the neutral return
path from the switchboard to the
power pole will be 100 volts AC.
Hmm. So the Neutral link will be
floating at 100 volts AC above
earth. And all the earths from the
various points in the house are connected to the Neutral link. So every
appliance plugged in will have have
its chassis floating at 100 volts AC
above earth - a lethal situation!
So your fridge, washing machine,
toaster and microwave oven could
all be sitting there silently with
their metal cabinets at a substantial voltage above earth. Touch one
of those and a properly earthed
metal object, such as your kitchen
sink, at the same time, and it could
be curtains!
It does happen
Don't think that the this scenario
is a remote possibility. It happened
very recently to a close acquaintance of yours truly. We'll call him
Jacko, to protect the innocent. He
discovered just such a fault condition had occurred in his home but
the reason why no-one had been
electrocuted was that his washing
machine was separately earthed
via a water-pipe just outside his
laundry.
If he hadn't been the naturally
super-cautious person he is, and
had not earthed his washing
machine separately, years ago, someone could be dead today.
But there is more to the story.
Having become aware of the
dangerous situation with the Earth
NOVEMBER 1987
79
parently thinks that current flows
into an appliance but not out of it.
Eventually, Jacko was able to explain the situation in words of less
than two syllables and persuaded
said inspector to measure the current in Active, Neutral and Earth,
using his tong tester (we'll explain
that in a moment). Result: 10 amps
in Active, 10 amps in Earth, zero
amps in Neutral; inspector perplexed but agrees that something is
wrong with the Neutral.
Enter council linesman. He
renews neutral connection at eaves
of house, pronounces situation fixed, leaves. Enter another inspector,
tests for current in neutral return,
finds none. Problem at power pole.
Several days later another pair of
linesmen return to renew the active
and neutral connections at both the
house and power pole. The saga
goes on.
At the time of writing, an inspector is due to return and pronounce
the installation safe . So far, six people from the supply authority have
been involved. If all houses in
Sydney had to be checked and rectified, it could take a hundred years
at this rate.
What you should do
These two photos show a quick and dirty approach to making a clamp-on
meter. The top shows an old relay with the active lead inserted, while below is
a transformer doing the same job.
and neutral return, our friend Jacko
contacted the local electricity supply authority to have the situation
rectified. Their reaction does not
inspire confidence.
On being told that the neutral
return was high resistance, the
first inspector tested the line with a
test-lamp which tests for the
presence of voltage only. On detecting the presence of voltage across
the active and neutral, he pronounced the situation normal. No
problem. On being told that all the
current from a 10-amp load was going via the Earth instead of neutral
he apparently had difficulty comprehending the situation.
(It should be noted here that a
test lamp is a very crude test instrument which is essentially a neon
80
SILICON CHIP
lamp. It tells the user if there is
more than about 90 volts peak present. It does not give any indication
of just how much voltage is present.
Inspectors seem to place undue
reliance on such crude instruments.
Enter another inspector, more
senior than the first. On having the
problem explained to him, and on
being asked to measure the currents in active and neutral his
response was, "I can measure the
current in the Active but I can't
measure current in the Neutral
because it is all used in the appliance"! Hmm.
Here we have a big problem.
Here is a senior electrical installation inspector who apparently does
not know how current flows! Heap-
Do you know where your main
earth point is? Take a walk around
your house. Where does the water
pipe enter the house? That is probably the point where you will find
the earth wire connected via a
screw clamp. If you can't find it,
have a look at your switchboard.
There should be a note (in white
paint) saying where the earth is.
For example, in the author's switchboard, the note says, "Main
earth under hall" and lo and
behold, if you went under the house
(it is partly two-storey) there you
would find the earth wire clamped
to the water pipe.
In some areas where the water
service is run in plastic pipe, the
authorities specify that the earth
connection is made to a long
copper-clad steel spike or rod
driven at least 1.2 metres into the
ground. Alternatively, the earth
connection may be made to a strip
electrode at least three metres in
length and buried at least 45cm
underground.
When you find the connection, inspect it carefully to see that it is
sound and not corroded. If the connection is badly corroded you
should have it attended to by a
licensed electrician. Alternatively,
the earth wire should be cleaned up
and reconnected. But before
Current flow, 3-phase and all that
touching it you should switch off
the power with the main switch on
your switchboard. If you have
another switch, such as for an offpeak hot water service, switch that
off too.
The reason for switching
everything off is to avoid the
possibility of having any current
flowing in the earth path when you
disconnect it. If current was flowing, and the neutral path was poor,
you would produce exactly the
hazardous situation we have
described above.
Alright, having determined that
your earth connection is satisfactory, how do you check the neutral
The second simplification
involves the concept of neutral
current flowing back to the substation, pole transformer or
whatever. This ignores the fact
that domestic mains power
distribution from the power pole
has three phases, each of
24OVAC (with 120 degrees phase
difference between each) . In an
ideal system, the currents should
be balanced so that there is no
current flowing in the neutral line.
Domestic systems are never
ideal though, so appreciable
current does flow in the neutral.
We have made a number of
simplifications in the writing of this
article. The first is that we have
said that current flows from active
to neutral or from active to Earth,
as the case may be. In fact, since
we are talking about 5OHz
alternating current, the current
changes its direction 1 00 times a
second.
It is convenient to think of
current flowing from the active line
though, because in the words of
an electrician we know, "It's the
activ_e line that gets ya. It's the one
with the juice!"
regard themselves as familiar with
mains wiring.
But there is a way of checking it.
There is only one safe and legal
way and that is to use a clip-on
meter (also known as a tong tester.)
return path? At this point we must
warn that you must not even think
of tampering with the wiring of
your switchboard. Not only is it illegal but it could be extremely
dangerous, even to those who
Special "First Issue" Offer to 'Silicon Chip' readers only!
150Amp Clamp-On Current
Probe for just $97.75?1}:S':
To coincide with the first issue of 'Silicon Chip' and this special feature on electrical
safety, Elmeasco have obtained a limited quantity of clamp on current probes.
The Model 4000P is a current transformer capable of measuring
ac current up to 150A without breaking the circuit under test.
You simply clip the probe to the conductor - just
like a clothes peg! The probe connects to
any multimeter (lead and plugs supplied)
capable of measuring 200mA. In fact the
reading on the multimeter will directly
correspond. Thus a SA current in the
conductor will give a meter reading ·
of 5mA. You can use the probe with
conductors up tq 11 mm in diameter.
If you've read the article, you'll know what
a great safety accessory this probe can be.
Contact your local Elmeasco Office.
Model 4000P
Specification
Current range : 1A to 150A
Accuracy : ± 2.5% + 0.15A
Division Ratio : 1000:1
Working Voltage : 300V ac rms max
Maximum Conductor Size : 11 .1mm (7/16in)
ELMEASCO Instruments Pt,,. Ltd.
Cheques &
Bankcard
Welcome
NEW SOUTH WALES
VICTORIA
QUEENSLAND
SOUTH AUSTRALIA
WESTERN AUSTRALIA
15 McDonald Street,
MORTLAKE
P.O.Box 30, CONCORD
NSW2137
Tel : (02) 736 2888
Telex : AA25887
Fax : (02) 73 3663
12 Marooncah Highway,
RINGWOOD
P.O.Box 623, RINGWOOD
VIC 3134
Tel: (03) 879 2322
Telex : AA30418
Fax : (03) 879 8688
192 Evans Road,
SALISBURY
P.O.Box 274 SALISBURY
OLD4107
Tel : (07) 875 1444
Telex : AA44062
Fax: (07) 277 375:i
241 Churchill Road,
PROSPECT
P.O.Box 154 PROSPECT
SA5082
TEL : (08) 344 9000
TELEX : AA87519
FAX : (08) 269 6411
Scott House, 46-48 Kings Park Road,
WEST PERTH
P.O.Box 901, WEST PERTH
WA0005
Tel : (09) 481 1500
Telex: AA94765
Fax : (09) 321 3026
NO VE MBER 1987
81
The Fluke 80i-410 clamp-on current probe is intended for use with digital
multimeters and will measure up to 400 amps AC and DC.
It can measure alternating current
through a cable without having to
break the connection.
Now many readers probably
have not heard of a clip-on meter let
alone have access to one but we'll
address that problem a little later.
In fact there is no need to
measure the current in the neutral
return. What needs to be done, and
which is a lot easier, is to measure
the current in the earth wire to the
water pipe.
As illustrated in one of the accompanying photos, a clip-on meter
does not have meter prods but has a
pair of clamp jaws which close
around a cable to measure that current. The clamp jaws actually constitute the core of a current
transformer. The ea ble to be
measured forms the primary winding of the transformer while the
meter monitors the secondary winding in the instrument.
One of the cheapest available
clip-on meters is the Tandy model
(Cat No 22-161) which currently
sells for $64.95.
Checking the earth current
Measuring the earth current is
simply a matter of fitting the clip-on
meter over the earth wire to the
water pipe, or over the water pipe
itself (between the earth wire connection and the point where the
pipe enters the ground), if that is
possible. But before you do that you
must be sure that your load current
is known. The way to do that is
switch off all appliances and light
fittings in your house, plus the hot
water system. Then connect a large
heating appliance of known rating.
82
SILICON CHIP
If possible, use a 2400W
radiator, on its highest setting. This
will draw a current of close to 10
amps, depending on the value of the
mains voltage and the tolerance on
the heating element.
So with the 2400W radiator switched on, you know you have a current from the Active of 10 amps.
The question is, what is the neutral
current? Measure the current in
the earth wire, subtract it from 10
amps, and you have the answer. If
the earth current is more than say,
5 amps, you have cause for concern. In that case, you should contact your local electricity authority
and have them check out your
neutral connection.
Don't do this test during or just
after wet weather. When the
ground is saturated, more current
will tend to flow via earth than via
the neutral path.
Most readers will not have access to a clip-on meter but as we
have found, it is possible to cobble
up a meter circuit to do the job. For
one example, we used the core and
winding of an old relay and for
another, we used a small
transformer with part of its windings removed. The object of the exercise is to modify (or butcher) the
relay or transformer so that you
can fit an earth wire within the
magnetic circuit of the core.
In the case of the relay, we
loosened the screw holding the coil
to the armature so that a wire could
be slipped into place and then retightened the screw. The voltage
developed by the relay coil is then
measured across the coil terminals.
Similarly, for the transformer,
the clamp(s) holding the laminations
in place is first removed, then the
coil can have turns removed to
allow space for the abovementioned wire to be slipped into place. The
transformer is then reassembled to
allow the measurement to be
performed.
The only problem with this
method, crude and simple as it is, is
that you need to calibrate it. Well,
this is fairly straightforward and
can use the same 2400W radiator,
or whatever, as a reference load.
You will need a short three-core
extension cord fitted with plug and
socket. The idea is to separate out
the active cable from the power
cord and insert it into your cobbled
up version of the clip-on meter.
Then plug in the radiator and take a
note of the reading generated by
the coil. This can then be used as a
rough guide to the current being
measured in the earth wire. Note
that it is a rough guide only as such
a measuring set-up is unlikely to be
linear.
Warning
Many people will not be qualified
or feel confident to make any
measurements as described in this
article. If they suspect that their
electrical wiring is unsafe, they
should contact a licensed electrician or the electricity supply
authorities.
A number of serious questions remain to be answered. Do the electricity supply authorities have any
program for periodic checking of
customers' Active, Neutral and
Earth connections? Or does the
first indication come from the
customer, complaining that they
"got a tingle from that appliance"?
And are plumbers and employees of
the various Water Boards instructed to take any special electric al safety measures when
disconnecting a customer's water
supply?
In the light of this article there is
a previously unsuspected hazard to
plumbers and Water Board
authorities as well as to the public
in general. If readers have any further information on this subject
which should be published, please
write to us at Silicon Chip, PO Box
139, Collaroy Beach, NSW 2097.
|